0x7694
EPM data: new PU size detected
Lenze · i550 protec Drive
What does 0x7694 mean?
This fault indicates that the parameter settings in the memory module originate from an inverter with different hardware, for example, a different power rating. The data is loaded into RAM without modification, and while compatible, requires user acceptance.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Execute "Save user data" (0x2022:003, P700.03) or "Save OEM data" (0x2022:006, P700.06) device command to accept and save the loaded settings for the new hardware.
Source: Lenze i550 protec Drive