0x2382

Fault - Device utilization (ixt) too high

Lenze · i550 protec Drive

What does 0x2382 mean?

This fault indicates that the inverter's device utilization (I²t) is excessively high, typically caused by frequent and/or prolonged acceleration processes. This condition is configurable and causes the inverter to disable immediately, requiring a 3-second blocking time before a reset.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    In applications with high mass inertias, reduce the maximum current of the inverter (0x6073, P324.00) to 150% of the nominal current.

Source: Lenze i550 protec Drive
Open Manual (Page 615)