065

CE4

Lenze · EVF9300 Vector Drive

What does 065 mean?

The controller has entered a BUS-OFF state on the system bus (CAN) due to receiving too many faulty telegrams, leading to disconnection from the bus. This indicates a severe communication breakdown.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Verify the PE (Protective Earth) connection.

  2. 4

    Check the CAN bus load and reduce the baud rate if necessary, observing cable length limitations.

  3. 5

    Switch off monitoring by setting parameter C0595 = 3.

Source: Lenze EVF9300 Vector Drive