x032
LP1 Motor phase failure
Lenze · 9300 Servo Controller
What does x032 mean?
One of the current-carrying motor phases has failed. This monitoring function is primarily for asynchronous motors and requires the MLP1 function block to be entered in C0465. Possible causes include a faulty motor, a damaged motor cable, or a current limit value (C0599) set too low. The monitoring can be switched off via C0597.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If the current limit value is set too low, increase the value via parameter C0599.
- 4
Verify that the function block MLP1 is correctly entered in C0465 if this monitoring is intended.
- 5
If temporary bypass is needed, set monitoring parameter C0597 = 3 to switch off the monitoring.
Source: Lenze 9300 Servo Controller