182

Fieldbus Motor Phase Failure (Warning)

Lenze · 8200 Series

What does 182 mean?

The drive has detected a motor phase failure and issued a Warning, indicated via the fieldbus interface. This means one or more motor phases are inactive or drawing insufficient current, but the drive may still be operating or preparing to trip. It requires prompt attention to prevent potential motor or drive damage if the condition persists.

Common Causes

  • Intermittent or partial open circuit in one motor phase connection, leading to current imbalance without complete loss.
  • Degradation of motor winding insulation causing leakage current, which can be interpreted as reduced phase current by the drive.
  • Slight imbalance in the power grid feeding the motor, leading to slightly differing phase currents.
  • Drive's current sensing parameter (e.g., P3-10 'Phase Imbalance Warning Threshold') is set too sensitively for the application.
  • Loose connection at the drive's output terminal (U, V, or W) or motor terminal, causing increased resistance in one phase.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Access the drive's current monitoring parameters (e.g., P1-03 'Output Current U', P1-04 'Output Current V', P1-05 'Output Current W') and observe phase currents for imbalance.

  2. 2

    Tighten all motor power connections at the drive output terminals (U, V, W) and motor terminals (U, V, W) to specified torque settings.

  3. 3

    Measure the resistance of each motor winding (U-V, V-W, W-U) with an ohmmeter and compare for deviations greater than 5% (indicating a motor winding issue).

  4. 4

    Review and adjust the drive's phase imbalance warning threshold parameter (e.g., P3-10 or similar) if it is set excessively low for the application's tolerance.

  5. 5

    Perform an insulation resistance test on the motor cable and windings to check for early signs of insulation breakdown.

  6. 6

    Monitor incoming supply voltages (L1, L2, L3) for balance; an imbalance greater than 2% can cause motor phase current imbalance.

Browse all codes in this manual (40)
Verified technical data. Last updated: March 2026

Related Faults

Lenze Error 182: Fieldbus Motor Phase Failure (Warning) — Troubleshooting Guide | ErrorLib