MOTOR CABLE Ax

Motor Cable Fault

Kuka · KR C2 Robot Controller

What does MOTOR CABLE Ax mean?

This error indicates a power unit overcurrent due to a short-circuit or ground fault, detected by hardware monitoring. It can also signify a ground fault detected by software monitoring, affecting the motor cable or motor itself.

Repair Steps

  1. 1

    Perform a visual inspection of the motor cable for the specified axis (Ax) for visible damage, insulation breaches, short circuits, or ground faults.

  2. 2

    Measure insulation resistance between motor phases U-V, V-W, U-W and each phase to ground using a megger – expect >1 MΩ.

  3. 3

    Check the motor itself for internal faults that could cause a short circuit or ground fault.

Browse all codes in this manual (54)
Verified technical data. Last updated: March 2026