32

LP1-Trip (Phase Failure)

Kuka · KR C2 Robot Controller

What does 32 mean?

This fault indicates a phase failure. For the KPS-600, it specifically refers to a mains phase failure, meaning an issue with the incoming AC power supply. For KSDs, it indicates a motor phase failure, meaning one or more phases supplying the motor are missing or unbalanced. Both conditions prevent proper operation and lead to drive shutdown.

Repair Steps

  1. 1

    Measure the voltage of each incoming AC mains phase (L1-L2, L2-L3, L3-L1) at the drive input terminals.

  2. 2

    Verify voltage balance between phases — expect less than 2% deviation.

  3. 3

    Measure the voltage of each motor output phase (U-V, V-W, U-W) during a run command.

  4. 4

    Inspect all power connections from the mains supply to the drive and from the drive to the motor for tightness and corrosion.

Browse all codes in this manual (54)
Verified technical data. Last updated: March 2026