443 n AXIS: CNV. COOLING FAN FAILURE

CONVERTER COOLING FAN FAILURE

Fanuc · Series 0i-D/0i Mate-D Maintenance

What does 443 n AXIS: CNV. COOLING FAN FAILURE mean?

This warning signal on the Fanuc Series 0i-D/0i Mate-D αi servo system indicates a failure of the converter cooling fan. This condition (SVWRN4 and SVWRN3 active) will lead to a converter overheat alarm if not addressed.

Common Causes

  • Cooling fan motor failure in the converter unit.
  • Obstruction or blockage of the fan's intake or exhaust, reducing cooling efficiency.
  • Loose or damaged electrical connection to the converter cooling fan.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Visually inspect the converter cooling fan for any blockages from dust or debris, and check for physical damage to the blades.

  2. 2

    Verify the power connections to the converter fan for tightness and absence of corrosion.

  3. 3

    Observe the fan's operation during power-on; check for proper rotation and absence of abnormal noise.

  4. 4

    Ensure that the air passages for the converter cooling are clear and unrestricted.

  5. 5

    If the fan is determined to be defective or not functioning, replace the converter cooling fan unit.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults

Source: Fanuc Series 0i-D/0i Mate-D Maintenance
Fanuc Error 443 n AXIS: CNV. COOLING FAN FAILURE: CONVERTER COOLING FAN FAILURE — Troubleshooting Guide | ErrorLib