24EXT
Emergency Stop Circuit 24V Fault
Fanuc · R-30iB Mate + Mate Plus Robot
What does 24EXT mean?
The 24EXT (Red) LED turning on indicates that the fuse (FUSE2) is blown, and the 24V external power supply (24EXT) for the emergency stop circuit is not being supplied. This impacts the integrity and functionality of the emergency stop line, posing a safety risk.
Repair Steps
- 1
If the fuse (FUSE2) has not blown, check the voltage between EXT24V and EXT0V at TBOP19. If no external power supply is used, check the jumper pin between EXT24V and INT24V or between EXT0V and INT0V.
- 2
Check the 24EXT (emergency stop line) for a short circuit or connection to ground.
- 3
Replace the emergency stop board.
- 4
Check the teach pendant for faults and replace if required.