08

Regeneration Excess Alarm

Fanuc · Alpha i Series AC Servo Motor and Spindle

What does 08 mean?

This alarm may be generated in the αi PSR when the spindle decelerates, particularly if a regenerative discharge unit with a resistance of 16Ω is used with a spindle motor having a maximum output of 5 kW or more. This indicates that the unit is not effectively dissipating regenerative energy.

Common Causes

  • Excessive regenerative energy during deceleration exceeds system limits.
  • Regenerative braking torque too high for controller's capacity.
  • Parameter settings for regeneration threshold (e.g., P3-01) are too low.
  • Faulty regenerative braking resistor system unable to dissipate excess energy.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the maximum output of the spindle motor. If it is 5 kW or more, proceed to the next step.

  2. 2

    Check the resistance of the installed regenerative discharge unit. If it is 16Ω, replace it with an 8Ω regenerative discharge unit.