Traduciendo...
TiM

Keypad Time Not Set

Yaskawa · V1000

¿Qué significa TiM ?

This fault appears when a keypad containing a battery is connected, but its internal date and time settings have not been configured or are incorrect. While this fault does not directly impact the drive's motor control functions, it can affect the accuracy of event logging and timestamping for troubleshooting purposes. Parameter o4-24 [bAT Detection Selection] determines if this detection is enabled.

Causas comunes

  • New keypad installed without initial date and time configuration.
  • Keypad battery completely discharged, causing loss of real-time clock (RTC) settings.
  • Internal keypad RTC data corruption due to voltage fluctuations or prolonged power loss.
  • Keypad firmware requiring time synchronization after an update or reset.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Navigate to the keypad's 'Time/Date Settings' menu (specific path varies by keypad model).

  2. 2

    Set the current date (DD/MM/YYYY) using the keypad navigation buttons.

  3. 3

    Set the current time (HH:MM:SS) using the keypad navigation buttons.

  4. 4

    Confirm the settings are saved and the fault clears after configuration.

Ver todos los códigos en este manual (87)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas