Overtorque Detection 2
Yaskawa · V1000
¿Qué significa oL4 ?
This fault triggers when the drive's output current surpasses the level set in L6-05 for longer than the time specified in L6-06. Similar to oL3, it points to a machine issue, such as a locked rotor or improperly set load parameters. Persistent overtorque can lead to mechanical strain, premature equipment wear, or even motor damage.
Causas comunes
- Severe mechanical jam or locked rotor condition in the driven equipment.
- Rapid deceleration rate (e.g., C1-02) set too fast, causing regenerative braking current to exceed limits, especially with large inertia loads.
- Incorrect overtorque detection level (L6-05) set too low, or overtorque detection time (L6-06) set too short.
- Motor braking circuit (if external brake resistor is used) malfunctioning or resistor value incorrect (e.g., R1-01).
- Internal short circuit within the motor windings leading to high current draw.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
1. Isolate the motor from the mechanical load and attempt to run the motor unloaded to distinguish motor/drive issue from mechanical load issue.
- 2
2. Monitor the drive's output current (e.g., U1-06) and the motor speed (e.g., U1-01) just before the fault occurs.
- 3
3. Increase parameter L6-05 (Overtorque Detection 2 Level) or L6-06 (Overtorque Detection 2 Time) in small increments if no mechanical issue is found.
- 4
4. If using a braking resistor, verify its resistance with an ohmmeter and check parameter R1-01 (Braking Resistor Ohms) matches.
- 5
5. Adjust deceleration time parameter C1-02 to a longer duration to reduce peak braking current demands.
- 6
6. Measure the resistance between each motor phase winding (U-V, V-W, W-U) with a multimeter (power off) and compare to specifications.