CP2

Comparator 2 Limit Error

Yaskawa · V1000

¿Qué significa CP2 ?

This fault triggers when the monitored value, chosen via H2-26 [Comparator 2 Monitor Selection], is found to be outside the acceptable operating range defined by H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit]. This indicates a critical process parameter has deviated beyond its safe boundaries, suggesting a potential malfunction or abnormal system state that could lead to operational instability if not corrected.

Causas comunes

  • The process variable monitored by H2-26 (Comparator 2 Monitor Selection) has fallen outside its safe operating limits.
  • Incorrect H2-27 (Comparator 2 Lower Limit) or H2-28 (Comparator 2 Upper Limit) settings are defined.
  • The sensor providing the input for the monitored parameter is malfunctioning or out of calibration.
  • Sudden, significant load changes or process disturbances pushing the variable beyond its allowed range.
  • Software bug or incorrect scaling configuration in the drive's parameter mapping for the monitored value.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Identify the parameter selected by H2-26 (e.g., U1-01, U1-03) and monitor its current value.

  2. 2

    Verify H2-27 (Comparator 2 Lower Limit) and H2-28 (Comparator 2 Upper Limit) are correctly set for the application.

  3. 3

    Check the calibration and accuracy of the external sensor providing the input to the monitored parameter.

  4. 4

    Observe the actual process variable for stability and ensure it stays within expected bounds during operation.

  5. 5

    Adjust H2-27 and H2-28 to encompass the true acceptable operating range for the monitored process variable.