Uv2

Control Power Supply Undervoltage

Yaskawa · P1000

¿Qué significa Uv2 ?

The drive detected an undervoltage condition specifically in the control power supply circuit. This affects the internal logic and control functions of the drive.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the main input voltage (L1-L2, L2-L3, L3-L1) at the drive's R/L1, S/L2, T/L3 terminals and verify against the nominal supply voltage.

  2. 2

    Inspect all main power input wiring connections at the drive terminals and upstream power distribution for looseness, corrosion, or signs of damage.

  3. 3

    Verify drive parameters related to input voltage settings and undervoltage trip levels (e.g., L1-01, L2-01) match the actual system supply and electrical drawings.

  4. 4

    If the drive utilizes a separate auxiliary control power input (e.g., 24VDC or 110VAC control source), measure its voltage at the dedicated terminals and confirm it is within specified operating limits.