EF0
Option External Fault
Yaskawa · P1000
¿Qué significa EF0 ?
This fault occurs when the drive loses communication, and parameter F6-03 is configured to stop the drive. Specifically, if the time between messages exceeds the Cable Loss Timeout (AO 21) interval, the drive declares EF0 and sets the speed command (AO 1) to 0, stopping according to F6-03 settings.
Causas comunes
- Time between communication messages exceeded Cable Loss Timeout (AO 21)
- Communication Fault Enable (BO 11) is 'On'
- Parameter F6-03 is set to 0, 1, or 2, determining the stopping method
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the communication line integrity and master device operation.
- 2
Check parameter AO 21 (Cable Loss Timeout) for appropriate interval setting.
- 3
Verify parameter BO 11 (Communication Fault Enable) is set to 'On' if this fault behavior is desired.
- 4
Check parameter F6-03 to understand the stopping method (0=Ramp, 1=Coast, 2=Emergency Stop).
Datos técnicos verificados. Última actualización: March 2026