Motor Overheat
Yaskawa · J1000
¿Qué significa oH3 ?
The motor overheat signal, typically from a PTC thermistor input to a multi-function analog terminal (H3-02, H3-06, or H3-10 = E), has exceeded its alarm level. Possible causes include faulty motor thermostat wiring, a locked-up machine, or the motor itself overheating due to excessive load or an inappropriate V/f pattern. Continued operation with an overheated motor risks winding insulation breakdown and costly motor failure.
Causas comunes
- Actual motor overheating due to sustained overload, insufficient cooling, or high ambient temperature.
- Faulty PTC thermistor inside the motor providing an erroneous high resistance signal.
- Wiring fault (e.g., open circuit, high resistance) in the thermistor cable to H3-02, H3-06, or H3-10.
- Incorrect configuration of the multi-function analog input parameter (H3-02, H3-06, or H3-10 = E).
- Inadequate sizing of the motor for the mechanical load requirements.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the resistance of the motor's PTC thermistor directly at the motor terminal box.
- 2
Measure the resistance of the thermistor feedback cable at the drive's input terminal (H3-02, H3-06, or H3-10).
- 3
Verify parameter H3-XX (Multi-Function Analog Input) is correctly set to 'E' (PTC Thermistor Input).
- 4
Check the motor's surface temperature using an infrared thermometer; compare to its rated operating temperature.
- 5
Inspect the motor for proper ventilation and clear cooling fins, removing any accumulated dust or debris.
- 6
Monitor drive output current and motor speed during operation to identify sustained overload conditions.