HWL
High Water Level
Yaskawa · iQpump1000
¿Qué significa HWL ?
The digital input configured for “High Water Level” (H1-oo = 90) is active. This fault indicates that the physical water level is high, or parameter P1-31 (High Water Digital Input Configuration) is programmed incorrectly.
Causas comunes
- The High Water Level switch is activated.
- P1-31 (High Water Digital Input Configuration) is programmed incorrectly.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Lower the water level.
- 2
Adjust the High Water Level switch physically.
- 3
Verify parameter P1-31 (High Water Digital Input Configuration) is correctly programmed.
Datos técnicos verificados. Última actualización: March 2026