EF

Forward/Reverse Run Command Input Error

Yaskawa · iQpump1000

¿Qué significa EF ?

Both forward run and reverse run commands have been received simultaneously and maintained for longer than 0.5 seconds. This is a sequence error that causes the motor to ramp to a stop, indicating conflicting commands from the control system.

Causas comunes

  • Simultaneous activation of both forward and reverse run commands for more than 0.5 seconds
  • Improper control sequence for run commands from the PLC or control system

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Review the control sequence for forward and reverse run commands from the PLC or control system.

  2. 2

    Verify that simultaneous activation of both forward and reverse commands for more than 0.5 seconds is prevented by control logic or wiring.

  3. 3

    Correct any identified sequence errors in the control program or wiring to ensure only one run command is active at a time.