Yaskawa iQp1000

3 códigos de falla documentados

HFB

High Feedback Fault

The iQpump VTC initiates a “High Feedback Fault (HFB)” when the feedback level rises above the programmed level (P1-11) for a time specified in P1-12. Upon fault occurrence, the iQpump VTC will coast to a stop. This function is active during running in all operation modes.

LFB/LW

Low Feedback/Water Fault

The iQpump VTC displays a “Low Feedback/Water (LFB/LW)” fault when the feedback level falls below the programmed level (P1-08) for a time specified in P1-09. When this fault occurs, the iQpump VTC will coast to a stop. This function is only active during running while operating in the auto mode.

Pre-charge

Pre-charge Alarm

The iQpump VTC operator display indicates a “Pre-charge” alarm when the pre-charge function is active. The iQpump VTC will stop when the feedback signal rises above the P4-01 level, the pre-charge timer P4-03 expires, or the low water digital input (H1-XX = 85) is deactivated. This alarm is only active in the stopped mode.

About·Privacy·Terms

ErrorLib — Biblioteca de códigos de falla industriales

Descargo de responsabilidad: ErrorLib es una herramienta de referencia técnica independiente. Aunque buscamos la precisión, verifique siempre con los manuales de servicio oficiales del fabricante antes de realizar mantenimiento en equipos industriales. ErrorLib no está afiliado con las marcas listadas.