Traduciendo...
UL3

Undertorque Detection 1

Yaskawa · F7 Drive

¿Qué significa UL3 ?

The drive detected that its output current was continuously below the threshold set in L6-02 for longer than the time specified in L6-03, when L6-01 was configured for undertorque detection. This fault indicates that the connected motor is operating under an unexpectedly low load, potentially due to a mechanical issue or process change.

Causas comunes

  • Mechanical decoupling of the motor from its load (e.g., broken belt, coupling failure, pump running dry).
  • Process material flow stoppage (e.g., conveyor belt empty, fan damper fully closed).
  • Undertorque detection level (L6-02) set too high, triggering even under normal light load conditions.
  • Undertorque detection delay time (L6-03) set too short, causing nuisance trips during transient low current.
  • Drive's internal current measurement inaccuracy or drift.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Visually inspect the mechanical coupling between the motor and its load (e.g., belt tension, coupling integrity).

  2. 2

    2. Confirm the process being driven by the motor is operating normally and not in a no-load or extremely light-load condition.

  3. 3

    3. Use a clamp-on ammeter to measure the actual motor output current during normal light-load operation and compare it to the L6-02 setting.

  4. 4

    4. Adjust parameter L6-02 (Undertorque Detection Level 1) to a lower, more appropriate current threshold that reflects actual light-load operation.

  5. 5

    5. Increase parameter L6-03 (Undertorque Detection Time 1) to allow for temporary low current conditions without tripping the fault.

Ver todos los códigos en este manual (63)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas