Traduciendo...
OL4

Overtorque 2 Fault

Yaskawa · F7 Drive

¿Qué significa OL4 ?

This fault indicates that the motor load has exceeded the configured Overtorque 2 detection level (L6-05) for the set duration (L6-06). Similar to OL3 but using a secondary profile, it triggers based on L6-04 settings, causing the drive to shut down. This points to a mechanical obstruction, jamming, or excessive resistance in the driven equipment. If persistent, this can lead to motor and drive damage or mechanical failure of the connected machinery.

Causas comunes

  • Intermittent or transient mechanical overload on the driven equipment, exceeding the secondary overtorque threshold (L6-05).
  • Incorrect configuration of L6-05 (Overtorque 2 Detection Level) or L6-06 (Overtorque 2 Detection Time), potentially set too low or too short for specific operating conditions.
  • Application requiring high starting torque or rapid acceleration that momentarily exceeds the OL4 trip limits, even if normal running torque is acceptable.
  • Degradation of mechanical components (e.g., worn bearings, misalignment) leading to increased friction and torque demand over time.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Review machine operational logs for correlation between OL4 faults and specific load events (e.g., material feeding, sudden acceleration) or process stages.

  2. 2

    Using a power meter, measure the actual mechanical power output and motor current during the application's most demanding conditions.

  3. 3

    Adjust parameter L6-05 (Overtorque 2 Detection Level) to a value slightly above the peak transient operating current, or increase L6-06 (Overtorque 2 Detection Time) if momentary spikes are expected.

  4. 4

    Perform a current signature analysis on the motor to detect early signs of mechanical wear or motor winding degradation.

  5. 5

    Check for correct motor parameters (E1-01, E1-02, E1-03) and ensure the auto-tuning process has been successfully completed, providing accurate motor model data.

Ver todos los códigos en este manual (63)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas