GF

Output Ground Fault

Yaskawa · F7 Drive

¿Qué significa GF ?

The Drive has detected an output grounding current exceeding 50% of its rated output current (L8-09 = 1 enabled), indicating a current leakage to ground. This is typically caused by a short in the motor leads, motor windings, or a defective internal current sensor. A persistent ground fault poses a safety risk and can lead to damage to the motor or Drive components.

Causas comunes

  • Motor cable insulation breakdown due to aging, abrasion, or mechanical damage, causing a phase-to-ground short.
  • Water ingress or contamination in the motor terminal box causing a short to the motor frame.
  • Internal motor winding insulation failure, resulting in a short to the motor casing.
  • Incorrectly terminated motor cables, where a conductor accidentally contacts the conduit or motor frame.
  • Damaged Drive output IGBT (Insulated Gate Bipolar Transistor) to heatsink insulation.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Power down the Drive immediately. Disconnect all three motor leads (U, V, W) from the Drive output terminals.

  2. 2

    2. Use a megohmmeter (insulation resistance tester) to test the insulation resistance of each motor phase (U, V, W) to ground. Readings should be above 1 Megohm (1MΩ).

  3. 3

    3. Visually inspect the entire length of the motor cable for any signs of damage, cuts, or abrasions on the outer jacket.

  4. 4

    4. Open the motor terminal box and inspect for moisture, contamination, or loose/frayed wiring that could be contacting the motor frame.

  5. 5

    5. If insulation resistance tests pass for the motor and cable, reconnect the motor and verify parameter L8-09 (Ground Fault Detection) is enabled (set to '1').