PROFISAFE FDBACK Wiring/Integration Error
Wago · PROFISAFE Modules
¿Qué significa 16#75D6 (2) ?
This fault occurs when the F-CPU changes to STOP during a functional test and when using the FD_BACK function. It indicates a problem with the physical wiring or logical integration of the FDBACK signal within the application. The error specifically highlights issues related to the wiring of FDBACK inputs or incorrect programming enable settings for local safety tags.
Causas comunes
- Incorrect wiring or faulty integration of the FDBACK signal at the application level.
- Improper wiring of the FDBACK digital inputs, including configurations for ALL, ON, FEEDBACK (%Ix.x), or QBAD_FIO (%Ix.x).
- Incorrect programming enable setting configured as 'ON' when the application uses only local safety tags.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the physical wiring and logical integration of the FDBACK signal within the application.
- 2
Inspect the wiring of the FDBACK digital inputs for ALL, ON, FEEDBACK (%Ix.x), and QBAD_FIO (%Ix.x) configurations.
- 3
Check the programming enable setting and confirm it is correctly configured as 'ON' if only local safety tags are utilized.