Traduciendo...
2

Unsupported I/O Module Data Type

Wago · PFC200 PLC

¿Qué significa 2 ?

The controller has detected an I/O module whose data type is not supported by the current firmware. This could be due to outdated controller firmware or a defective I/O module itself. A flashing red I/O LED indicates the presence of a defective module.

Causas comunes

  • Outdated controller firmware not supporting the connected I/O module's data type
  • Defective I/O module presenting an unsupported data type to the controller

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Update the controller firmware to the latest available version.

  2. 2

    If the error persists, switch off the power supply to the controller.

  3. 3

    Implement a bisection method to identify the defective I/O module: Place the end module in the middle of the I/O modules and power on. If the I/O LED flashes red, repeat the process on the first half of the modules (towards the controller). If the LED is no longer flashing, repeat on the second half (away from the controller).

  4. 4

    Once the defective I/O module is isolated, replace that module.

Ver todos los códigos en este manual (23)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas