I/O module(s) has (have) identified internal bus command as incorrect (Fault code 3, argument 0)
Wago · Modular I/O System PROFIBUS DP
¿Qué significa I/O-LED 3-0 ?
One or more I/O modules connected to the Fieldbus Coupler have reported receiving incorrect internal bus commands. This indicates a critical communication issue on the internal bus, potentially due to a faulty module, corrupted signals, or a defective coupler, leading to unreliable data exchange.
Causas comunes
- Interruption or severe corruption on the internal communication bus
- Defective I/O module generating or interpreting incorrect internal bus commands
- Defective coupler sending incorrect commands or experiencing internal bus issues
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Disconnect the Profibus cable from the coupler to isolate internal bus communication.
- 2
Plug the end module into the middle of the node to segment the internal bus and identify the faulty section.
- 3
Cycle the coupler's supply voltage (off and on again).
- 4
If the I/O LED continues to flash, shift the end module again to further isolate the defective segment.
- 5
If only one module is connected to the coupler and the I/O Err LED illuminates, replace the single I/O module or the coupler, as one of them is defective.