Traduciendo...
BUS-LED 3-2
Excessive configuration data (Fault code 3, argument 2)
Wago · Modular I/O System PROFIBUS DP
¿Qué significa BUS-LED 3-2 ?
The Fieldbus Coupler has excessive configuration data, possibly due to a module being incorrectly configured multiple times or redundant data entries. This can result in configuration mismatches and operational issues, impacting coupler and module functionality.
Causas comunes
- A specific I/O module was incorrectly included multiple times in the configuration
- The loaded configuration data contains redundant or erroneous entries
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the configuration for any redundant or incorrect module entries.
- 2
Load the corrected configuration onto the coupler.
- 3
Cycle the supply voltage of the coupler (off then on again) to restart.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Wago Modular I/O System PROFIBUS DP