Traduciendo...
21

Low Temperature (Adv. Code 0)

Vacon · X4

¿Qué significa 21 ?

This fault is triggered when the heatsink temperature drops below -10.0 degrees Celsius. Operating the drive outside its specified low-temperature limits can affect the performance and reliability of internal components, particularly electrolytic capacitors and LCD displays. This prevents safe operation and could cause damage.

Causas comunes

  • Drive operating in an unheated environment with ambient temperature falling below the specified minimum operating temperature (e.g., -10°C).
  • Heatsink temperature sensor (thermistor) fault, causing it to report an artificially low temperature.
  • Ventilation system drawing in extremely cold air directly onto the drive's heatsink.
  • Drive enclosure not adequately insulated for cold environments or experiencing localized cold spots.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Measure the ambient temperature inside the control panel enclosure and directly around the drive's heatsink using a calibrated thermometer.

  2. 2

    2. Ensure the operating environment temperature is consistently within the drive's specified range (typically 0°C to 50°C for industrial drives).

  3. 3

    3. If the ambient temperature is genuinely low, consider installing a panel heater with a thermostat to maintain the minimum operating temperature inside the enclosure.

  4. 4

    4. Power down. Visually inspect the heatsink thermistor and its connections for damage or looseness.

  5. 5

    5. If the ambient temperature is above -10°C and the fault persists, the heatsink thermistor or its measurement circuit may be faulty.

Ver todos los códigos en este manual (33)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas