Vacon · NXS NXP

¿Qué significa 61 ?

The motor's actual speed deviates significantly from its commanded speed reference. This can be caused by a faulty encoder connection (if an encoder is used), or for Permanent Magnet Synchronous (PMS) motors, exceeding the pull-out torque. An uncorrected speed error leads to inaccurate motor control, poor process performance, and potential instability.

Causas comunes

  • Encoder feedback cable damage (e.g., open circuit, short circuit) or loose connection at drive or encoder.
  • Encoder sensor failure or contamination causing inconsistent pulse generation.
  • Incorrect encoder parameters (e.g., P1-20, P1-21 for pulse count) in the drive setup.
  • Motor shaft coupling slippage or mechanical load issue preventing motor from reaching commanded speed.
  • For PMS motors, incorrect motor parameters (e.g., P1-10, P1-11 for motor poles) or incorrect phase detection.
  • Excessive motor load exceeding drive's torque capabilities, leading to slip or inability to accelerate.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify all encoder cable connections (e.g., terminals 88, 89, 90 on drive) for proper seating and continuity using a multimeter.

  2. 2

    Measure encoder pulse output (e.g., channels A, B, Z) with an oscilloscope while rotating the motor slowly, checking for signal integrity.

  3. 3

    Confirm drive parameters P1-20 (Encoder resolution) and P1-21 (Encoder type) match the installed encoder specifications.

  4. 4

    Inspect motor shaft coupling for tightness and verify no slippage under load.

  5. 5

    For PMS motors, re-run auto-tuning (e.g., Parameter P1-30 set to '2' or '3') to ensure correct motor data is learned.

  6. 6

    Monitor drive's actual speed feedback (e.g., via LCP or software) and compare to commanded speed reference to quantify deviation.

Ver todos los códigos en este manual (54)