Traduciendo...
58

Brake

Vacon · NXS NXP

¿Qué significa 58 ?

The actual status feedback from the mechanical brake (e.g., open/closed) does not match the drive's control signal for the brake. This indicates a malfunction in the brake mechanism, its feedback sensor, or the associated wiring. A malfunctioning brake poses a safety risk and can prevent proper machine operation or holding.

Causas comunes

  • Mechanical brake wear or damage preventing full engagement or disengagement.
  • Brake feedback switch (e.g., limit switch) faulty, stuck, or misaligned.
  • Drive output voltage to brake coil (e.g., 24VDC) lost or below required level.
  • Brake coil internal short circuit or open circuit preventing proper current flow.
  • Parameter P3-12 (Brake control type) incorrectly configured for the brake hardware.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify drive output voltage to brake coil terminals (e.g., X1:1, X1:2) matches specified voltage (e.g., 24VDC) when commanded open/closed.

  2. 2

    Measure resistance of brake coil windings; compare to manufacturer's specifications (e.g., 20 Ohms).

  3. 3

    Actuate brake manually (if possible) and visually confirm mechanical movement and feedback switch activation.

  4. 4

    Test continuity of brake feedback switch contacts (e.g., on terminals X2:3, X2:4) in both open and closed states using a multimeter.

  5. 5

    Check drive parameter P3-12 for correct brake control configuration (e.g., '0 = No brake', '1 = Dynamic brake').

  6. 6

    Inspect brake mechanism for physical obstructions, wear, or damage to pads or spring assembly.

Ver todos los códigos en este manual (54)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas