Traduciendo...
42

Brake resistor overtemperature

Vacon · NXS NXP

¿Qué significa 42 ?

The brake resistor overtemperature protection has activated, indicating that the brake resistor is dissipating too much energy, likely due to overly heavy or frequent braking cycles. This condition can lead to premature resistor failure or a fire hazard if not addressed.

Causas comunes

  • Excessive braking frequency or deceleration rates (e.g., P2-02 set too low) causing high regenerative energy.
  • Brake resistor sizing insufficient for the application's duty cycle or inertia (e.g., resistor ohmic value too high or power rating too low).
  • Faulty brake choppers (e.g., internal transistor shorted or open) causing continuous current flow through the resistor.
  • Incorrect brake chopper parameters (e.g., P7-05 (Brake enable), P7-06 (Brake resistor value)) leading to inefficient energy dissipation.
  • External thermal protection sensor (if applicable) for the brake resistor being tripped or miscalibrated.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the resistance of the external brake resistor at terminals R+/RB to verify it matches the specified ohmic value (e.g., 20 Ohms).

  2. 2

    Check the brake resistor's physical temperature and inspect for signs of overheating (e.g., discoloration).

  3. 3

    Increase the deceleration ramp time (P2-02) to reduce the rate of energy regeneration.

  4. 4

    Reduce the braking duty cycle or implement mechanical braking assist if the process allows.

  5. 5

    Verify parameter P7-06 (Brake resistor ohmic value) matches the installed resistor's value.

  6. 6

    If the resistor is hot and correct, consider installing a larger power rated brake resistor or an external braking unit.

Ver todos los códigos en este manual (54)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas