Temperature sensor board 2 fault
Vacon · NXP AFE-II Drive
¿Qué significa F65 ?
The temperature protection function for sensor board 2 has detected an issue, which could be an exceeded temperature limit, an unwired or non-functional sensor, or a short circuit in the sensor wiring (A1-A3 conditions). This compromises temperature monitoring.
Causas comunes
- Actual temperature measured by the sensor connected to board 2 (e.g., gearbox oil, bearing) has exceeded its programmed trip limit (e.g., P3-11).
- Open circuit in the wiring connecting the temperature sensor (e.g., Pt100, NTC) to sensor board 2, indicating a broken wire.
- Short circuit in the temperature sensor wiring to sensor board 2, resulting in an invalid low resistance reading.
- Failure of the temperature sensor itself (e.g., internal break, resistance drift) providing incorrect feedback.
- Defective temperature sensor board 2, preventing accurate temperature measurement or communication.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the resistance of the temperature sensor connected to sensor board 2 (e.g., terminals T3, T4) and compare it to its specification (e.g., 100 Ohm for Pt100 at 0°C).
- 2
Inspect the wiring from the temperature sensor to sensor board 2 for any cuts, breaks, or loose connections at the terminal block.
- 3
Verify the actual temperature of the monitored component (e.g., gearbox casing) using an external infrared thermometer.
- 4
Review parameter P3-11 (Temperature Sensor 2 Trip Limit) to ensure it is set appropriately for the application and sensor type.
- 5
Temporarily disconnect the sensor wiring from sensor board 2 and connect a precision resistor (e.g., 100 Ohm) to simulate a healthy sensor, then observe the fault status.