Emergency stop

Vacon · NX Liquid-Cooled Drive

¿Qué significa 63 ?

An emergency stop command has been received either from a digital input or via fieldbus, indicating the E-stop feedback has triggered the fault.

Causas comunes

  • Emergency stop button activated.
  • Emergency stop circuit opened.
  • External signal triggering emergency stop.
  • Software emergency stop condition met.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the functionality of the Main Circuit Breaker (MCB) and associated trip mechanisms.

  2. 2

    Verify the signal wiring for the E-stop digital input or the integrity of the fieldbus connection and E-stop message.

  3. 3

    After the underlying cause of the emergency stop is resolved, reset the fault via the keypad or appropriate input.

  4. 4

    Issue a new run command to restart the drive's operation.