Traduciendo...
45
Option Board Type Mismatch
Vacon · NX Liquid-Cooled Drive
¿Qué significa 45 ?
An option board of a different or incorrect type has been detected in a slot. This indicates a hardware configuration mismatch between the inserted board and the expected or previously configured type. Subcodes S1-S5 specify the board type (Control, Control unit, Power board, Power unit, Adapter board & slot).
Causas comunes
- Installed option board is not recognized or incompatible.
- Option board wiring or connection issue.
- Incorrect option board type selected in parameters (P0450).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Reset the fault.
- 2
Verify the type of option board installed against the required or configured type for that slot.
- 3
Set the option board parameters again, ensuring they match the characteristics of the newly installed or corrected board.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Vacon NX Liquid-Cooled Drive