IGBT Saturation / Short Circuit

Vacon · 100 FLOW Application Guide

¿Qué significa 7 ?

This fault indicates a serious hardware failure such as a defective IGBT, a de-saturation short circuit within an IGBT, or a short circuit/overload in the brake resistor. This fault suggests significant damage to the power stage and continuing operation can cause further severe damage or injury.

Causas comunes

  • Catastrophic short circuit (phase-to-phase or phase-to-ground) on the motor output terminals (T1, T2, T3) due to damaged motor cables.
  • Internal failure of an Insulated Gate Bipolar Transistor (IGBT) module in the inverter bridge, leading to a short circuit condition.
  • Brake resistor short-circuited or overloaded, drawing excessive current from the DC bus and exceeding IGBT ratings.
  • Driver circuit fault within the IGBT gate drive unit, causing improper switching or saturation detection failure.
  • Excessive current demand from the motor beyond the drive's output capabilities, stressing the IGBTs.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Disconnect the motor cables (U, V, W) from the drive output terminals (T1, T2, T3).

  2. 2

    Measure the resistance between each output phase terminal (T1-T2, T2-T3, T3-T1) and from each phase to the PE terminal (ground). Look for near-zero resistance.

  3. 3

    If a brake resistor is installed, disconnect it and measure its resistance (e.g., terminals BR+ and BR-) for a short circuit or open circuit.

  4. 4

    With input power off and DC link discharged, perform a diode test across the IGBTs (from DC+ to T1, T2, T3 and from T1, T2, T3 to DC-) using a multimeter diode function.

  5. 5

    Inspect the cooling fan operation and heatsink for any obstructions or excessive dust buildup that could lead to overheating of the IGBT modules.

Ver todos los códigos en este manual (73)