Traduciendo...
45

Device Added (Different Type)

Vacon · 100 FLOW Application Guide

¿Qué significa 45 ?

A new power unit or option board (in slot C, D, or E) of a *different type* has been added or detected in the drive. Similar to 'Device changed (different type),' this means parameters for the new device are not saved or compatible, requiring initial configuration. Without proper setup, the added device will not function correctly.

Causas comunes

  • A new option board or power unit of a different type has been physically added to slot C, D, or E without the corresponding parameter configuration.
  • Parameter P2.1.1 (Slot C type), P2.2.1 (Slot D type), or P2.3.1 (Slot E type) is not correctly set to acknowledge the new device's type.
  • The drive has detected an unrecognized or incompatible device ID in an expansion slot (C, D, or E) that was previously empty or held a different device.
  • Incompatibility between the firmware of the newly added device and the drive's current main control unit firmware version.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Identify the newly added option board or power unit in slot C, D, or E and confirm its exact part number and intended function.

  2. 2

    2. Access parameter P2.1.1 (Slot C type), P2.2.1 (Slot D type), or P2.3.1 (Slot E type) and set it to the correct type for the installed device.

  3. 3

    3. Power cycle the drive after parameter adjustment and confirm the fault clears; then proceed with configuring the device-specific parameters.

  4. 4

    4. If the device was added unintentionally or is incorrect for the application, power down the drive and remove it from slot C, D, or E.

Ver todos los códigos en este manual (73)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Vacon 100 FLOW Application Guide