Unbalance

Vacon · 100 FLOW Application Guide

¿Qué significa 18 ?

This is a warning (not a fault trip) indicating an unbalance between power modules in paralleled units. Subcodes specify if the unbalance is in current or DC-Voltage.

Causas comunes

  • Unequal current sharing between parallel power modules in a multi-drive setup.
  • Mismatch in impedance between parallel power paths.
  • Failure or derating of one or more power modules.
  • Incorrect load balancing configuration.
  • Control loop instability affecting current distribution.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify impedance matching for all parallel power modules.

  2. 2

    Measure current output from each individual power module if possible.

  3. 3

    Check status of individual power modules for any signs of failure or derating.

  4. 4

    Confirm parameter settings for parallel operation are correctly applied to all drives.

  5. 5

    Ensure load distribution is balanced across all connected modules.

Ver todos los códigos en este manual (73)
Datos técnicos verificados. Última actualización: March 2026