Traduciendo...
3501/3601/3701

Ground Fault / High Leakage Current / Residual Current

SMA · Sunny Boy Solar Inverter

¿Qué significa 3501/3601/3701 ?

The inverter has detected a ground fault in the PV array (3501), or the leakage current of the inverter and PV array is too high (3601), or a residual current due to temporary grounding of the PV array has been detected (3701). These conditions indicate defective or insufficient electrical insulation from the PV system to ground, potentially from a ground fault, residual current, or a malfunction causing high leakage current. The inverter will interrupt feed-in operation.

Causas comunes

  • Ground fault in the PV array due to damaged insulation.
  • Defective or insufficient electrical insulation from the PV system to ground.
  • High leakage current in the inverter and/or PV array due to a malfunction or residual current from temporary grounding.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Disconnect the inverter from all voltage sources (refer to the inverter installation manual).

  2. 2

    Measure the voltage between the positive terminal and the ground potential (PE) of the PV array.

  3. 3

    Measure the voltage between the negative terminal and the ground potential (PE) of the PV array.

  4. 4

    Measure the voltage between the positive and negative terminals of the PV array.

  5. 5

    If all measured voltages are stable AND the sum of the two voltages to ground potential is approximately equal to the voltage between the positive and negative terminals, a ground fault is present. Determine the location of the ground fault via the ratio of the two measured voltages and eliminate it.

  6. 6

    If a definite ground fault cannot be measured by voltage, perform an insulation resistance measurement on the PV system using a measuring device with a DC input voltage range of 600 V or higher.

Ver todos los códigos en este manual (23)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas