XFMR

Transformer Connected to Wrong Grid Configuration

SMA · SUNNY BOY 5000US-8000US Solar Inverter

¿Qué significa XFMR ?

The Sunny Boy SB50US-80US-IUS094030's internal transformer is incorrectly connected or configured for the present grid type. This issue can manifest in Delta corner-grounded grids if the grid ground is not connected to terminal L2, or in unbalanced 208V/240V grids if L1 and L2 are interchanged.

Causas comunes

  • Incorrect transformer connection to the grid.
  • Grid ground not connected to terminal L2 in Delta corner-grounded grids.
  • L1 and L2 interchanged in unbalanced 208V and 240V grids.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the physical connection of the inverter's transformer to the grid terminals.

  2. 2

    In Delta corner-grounded grids, ensure that the grid ground is correctly connected to terminal L2.

  3. 3

    In unbalanced 208V and 240V grids, attempt interchanging the L1 and L2 connections to clear the error.