Traduciendo...
Vac-Bfr/Vac-Srr

AC Grid Voltage Outside Allowable Range

SMA · SUNNY BOY 5000US-8000US Solar Inverter

¿Qué significa Vac-Bfr/Vac-Srr ?

The AC grid voltage has exceeded or fallen below the allowable operating range for the Sunny Boy SB50US-80US-IUS094030. This can also be caused by a disconnected grid or a disconnected AC cable. The inverter assumes a public grid outage and disconnects to prevent islanding. 'Bfr' and 'Srr' are internal processor messages.

Causas comunes

  • AC grid voltage exceeding the allowed upper limit (>Vac Max).
  • AC grid voltage falling below the allowed lower limit (<Vac Min).
  • Disconnected public grid.
  • Disconnected AC cable to the grid.
  • Rapid change in grid voltage.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the condition of the grid at the AC terminal blocks within the Sunny Boy SB50US-80US-IUS094030.

  2. 2

    Inspect the AC disconnect between the Sunny Boy and the grid.

Ver todos los códigos en este manual (23)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: SMA SUNNY BOY 5000US-8000US Solar Inverter