TM150 Temperature Alarm Channel 9
Siemens · SINAMICS S120/S150 Reference List
¿Qué significa A35415 ?
This alarm is initiated when the actual temperature (r4105[9]) for channel 9 on Terminal Module 150 (TM150) exceeds its configured alarm threshold (p4102[18]). A timer (p4103[9]) is also started. The alarm will clear once the temperature falls below the threshold, factoring in the defined hysteresis (p4118[9]).
Causas comunes
- Overheating of the equipment monitored by channel 9 due to sustained high load or insufficient power supply characteristics (e.g., voltage imbalance).
- Alarm threshold p4102[18] configured with a value that is too low for the application's specific thermal profile.
- Damage or wear to the temperature sensor itself, causing it to report higher than actual temperatures.
- Poor contact or high resistance in the wiring between the temperature sensor and the TM150 module's channel 9 input.
- Malfunction of a heating element or an unintended heat source near the monitored component.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
1. Check the live temperature value r4105[9] in the diagnostic parameters of the control system.
- 2
2. Review and adjust parameter p4102[18] (alarm threshold) and p4103[9] (alarm timer) to match the component's thermal limits and operational requirements.
- 3
3. Use a thermal imaging camera to measure the surface temperature of the component connected to channel 9 to corroborate the sensor reading.
- 4
4. Verify the integrity of the wiring to TM150 channel 9, ensuring secure connections at terminals X1.19 and X1.20 (typical for channel 9).
- 5
5. Investigate for external heat sources or heating element malfunctions that could be affecting the monitored component.