Monitoring function not supported
Siemens · SINAMICS G120
¿Qué significa F01682 ?
A configured monitoring function is not supported by the current hardware or software version. This indicates a mismatch between desired functionality and system capabilities, preventing the function from operating correctly or safely.
Causas comunes
- Attempting to enable a monitoring function (e.g., Safe Brake Control SBC, Safe Operating Stop SOS) that requires an optional hardware module not installed on the drive.
- The drive's firmware version is outdated and does not include support for the specific safety or monitoring function being configured.
- Parameterization of a function (e.g., p9500 (SLS enable)) for which the connected motor module or control unit lacks the necessary processing capability.
- Incorrect selection of the drive type or control unit type during initial setup in the engineering software (e.g., STARTER).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
1. Verify that the installed hardware modules (e.g., Control Unit, safety modules) are compatible with the desired monitoring function.
- 2
2. Check the drive's firmware version (r0018) and compare it to the minimum version required for the monitoring function as per the manufacturer's documentation.
- 3
3. If the firmware is outdated, perform a firmware update to a compatible version using commissioning software (e.g., STARTER).
- 4
4. Deactivate the unsupported monitoring function by setting its enabling parameter (e.g., p9500) to 0 or an equivalent 'disabled' state.
- 5
5. Review the project configuration in the engineering software to ensure the correct hardware components are selected.