Traduciendo...
F01630

Brake control defective

Siemens · SINAMICS G120

¿Qué significa F01630 ?

The motor holding brake control is malfunctioning, posing a risk of uncontrolled motor movement. This can stem from an incorrect p1278 setting, disconnected or interrupted brake cables, a ground fault, or a short-circuit in the brake winding. A fault in the Safe Brake Relay, Control Unit, or Power Module could also be the cause.

Causas comunes

  • Incorrect setting of parameter P1278 (Brake control mode) for the specific motor or application.
  • Interruption or disconnection of the motor brake control cables (e.g., terminals X11/X12 or specific brake module connections).
  • Ground fault in the motor brake winding or its supply cabling.
  • Failure of the internal brake control relay or solid-state switch within the drive module.
  • Overcurrent or short circuit detected in the brake power supply circuit.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the setting of parameter P1278 (Brake control mode) according to the motor's technical specifications and the application's requirements.

  2. 2

    Measure the resistance of the motor brake coil directly at the drive's brake terminals (e.g., X11/X12) to compare with the specified value (e.g., 20-50 Ohms).

  3. 3

    Check for 24VDC or 400VAC (depending on brake type) output voltage at the brake terminals when the drive commands brake release (e.g., using a multimeter).

  4. 4

    Inspect the entire brake cabling path from the drive to the motor for signs of physical damage, loose connections, or insulation breakdown.

  5. 5

    Perform an insulation resistance test (Megger test) on the brake cables and motor brake coil to detect ground faults.

Ver todos los códigos en este manual (109)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas