Traduciendo...
F01625

Sign-of-life error in the Safety data

Siemens · SINAMICS G120

¿Qué significa F01625 ?

An error has occurred with the safety data's sign-of-life signal, indicating a potential communication or integrity issue within the safety functions. This can be caused by EMC disturbances or an inadmissible voltage at a Control Unit digital output. Such an error critically impacts the system's ability to maintain safe operation.

Causas comunes

  • Electromagnetic compatibility (EMC) interference affecting the safety communication bus or internal Control Unit communication.
  • Incorrect or inadequate shielding of safety communication cables (e.g., PROFIsafe line).
  • Processor overload or internal timing issues within the Control Unit preventing timely processing of safety sign-of-life signals.
  • Temporary communication disruption between the safety Control Unit and the safety application (e.g., Safety CPU).
  • Inconsistent safety configuration data (e.g., checksum mismatch) between the drive and the higher-level safety controller.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect and verify the shielding termination for all safety communication cables (e.g., PROFINET/PROFIBUS) at both the drive and controller ends.

  2. 2

    Check for potential sources of high-frequency interference (e.g., unsuppressed contactors, welding equipment) near the drive or safety communication lines.

  3. 3

    Verify the drive's firmware version is compatible with the safety PLC firmware and the configured safety functions.

  4. 4

    Perform a power cycle of the drive and the associated safety controller to re-initialize communication.

  5. 5

    Review event logs (e.g., drive fault memory and safety PLC diagnostic buffer) for concurrent communication issues or other related faults.

Ver todos los códigos en este manual (109)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas