Traduciendo...
C30770

Discrepancy error of the fail-safe digital inputs or the fail-safe digital outputs

Siemens · SINAMICS G120

¿Qué significa C30770 ?

A discrepancy error has been detected in either the fail-safe digital inputs or outputs, indicating inconsistent signals or faulty wiring. This compromises the reliability of safety-related I/O, potentially leading to incorrect safety reactions.

Causas comunes

  • Dual-channel fail-safe input (e.g., safety gate switch) channels (1 and 2) not switching within the parameterized discrepancy time (P30700).
  • Wiring fault (e.g., partial short, intermittent open circuit) affecting one channel of a dual-channel F-IO pair.
  • Faulty external safety device providing inconsistent signals on its redundant outputs.
  • Software configuration error where single-channel F-IO is incorrectly set as dual-channel, or vice versa (e.g., P30701).
  • Excessive electrical noise or inductive spikes causing momentary signal corruption on F-IO lines.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Identify the specific fail-safe input or output pair (e.g., F-DI0/F-DI1) causing the discrepancy error, referenced by r2124.

  2. 2

    Measure the voltage levels on both channels of the affected F-IO pair (e.g., X1:F-DI0 and X1:F-DI1) and observe their switching behavior simultaneously.

  3. 3

    Perform a continuity test on both wires of the dual-channel F-IO from the external safety device to the inverter's terminals to detect breaks or shorts.

  4. 4

    Temporarily bypass the external safety device with a known good input signal (e.g., 24VDC jumpers for F-DI) to isolate the device fault from wiring.

  5. 5

    Adjust the discrepancy time (P30700) if the external device has inherent switching delays, ensuring the delay is within safe limits.

  6. 6

    Verify the F-IO parameterization (P30701, P30702) matches the actual wiring and device type (e.g., 2-channel without test pulses).

Ver todos los códigos en este manual (109)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Siemens C30770 (Discrepancy error of the fail-safe digital… | ErrorLib