Traduciendo...
A01691

SLS signal inconsistency

Siemens · SINAMICS G120

¿Qué significa A01691 ?

An inconsistency has been detected in the safety input signals, specifically related to the Safe Limited Speed (SLS) function. The drive will initiate a controlled deceleration (SS1) and eventually enter a Safe Torque Off (STO) state, issuing a fault due to the potential compromise of safety integrity.

Causas comunes

  • Mismatch between redundant safety input signals for SLS (e.g., F-DI0 and F-DI1) indicating a fault in one of the channels.
  • Defective safety sensor or switch providing inconsistent feedback for the SLS function to the drive's safety inputs.
  • Cable breakage, short circuit, or high resistance in one of the safety input signal lines (e.g., between X150 terminal and safety sensor).
  • External safety relay or safety controller providing incorrect or inconsistent signals to the drive's safety inputs.
  • Internal fault within the drive's safety module responsible for monitoring SLS input signals and their redundancy.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Verify the state of the redundant safety input signals (e.g., F-DI0 and F-DI1) directly at the drive's safety terminals (X150) using a multimeter (24VDC expected).

  2. 2

    2. Check continuity and insulation resistance of the safety input cabling from the safety sensor or switch to the drive's X150 terminals.

  3. 3

    3. Test the external safety sensor or switch used for SLS by manually actuating it and observing signal changes at the drive's inputs.

  4. 4

    4. Inspect the drive's safety module diagnostic LEDs (if available) for specific indications of input channel failures or inconsistencies.

  5. 5

    5. Perform a safety test of the SLS function as per the drive's safety manual to identify the exact point of inconsistency in the safety chain.

Ver todos los códigos en este manual (109)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas