Unsuitable combination of motor and power unit
Siemens · SINAMICS G120
¿Qué significa A01669 ?
The combination of the motor and power unit is unsuitable, specifically if the ratio between the rated power unit current (r0207[0]) and rated motor current (p0305) is not greater than 5. This mismatch can lead to sporadic C01711 or C30711 messages and suboptimal performance or even damage over time.
Causas comunes
- Motor rated current (p0305) is significantly higher than the power unit's rated current (r0207[0]), violating the required ratio.
- Power unit selected is undersized for the connected motor's continuous current requirements.
- Incorrect motor data entry for p0305 during drive commissioning, leading to a calculated mismatch.
- Drive firmware or configuration expects a different motor/power unit scaling than what is physically installed.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
1. Verify the rated current of the connected motor from its nameplate and compare it to the value in parameter p0305.
- 2
2. Cross-reference the power unit's rated output current (r0207[0]) with its specifications sheet.
- 3
3. Recalculate the ratio (r0207[0] / p0305) and confirm it meets the minimum requirement of 5.
- 4
4. If the ratio is below 5, select a motor with a lower rated current (p0305) or a power unit with a higher rated output current (r0207[0]) to ensure compatibility.
- 5
5. Check for any unintended scaling factors or unit discrepancies in parameters related to current ratings.