F07
DC link overvoltage
SEW Eurodrive · MOVITRAC 07B System
¿Qué significa F07 ?
An immediate switch-off with inhibit occurs when the DC link voltage is excessively high. This often results from too much regenerative power, issues with the braking resistor circuit (supply cable or resistance value), or a ground fault.
Causas comunes
- DC link voltage too high
- Excessive regenerative power
- Issue with braking resistor circuit (supply cable or resistance value)
- Ground fault
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Extend deceleration ramps to reduce regenerative power
- 2
Check the supply cable to the braking resistor for continuity
- 3
Check the technical data of the braking resistor to ensure correct value
- 4
Eliminate any ground fault detected
Datos técnicos verificados. Última actualización: March 2026