91

Communication error between field-bus gateway and MOVIMOT®

SEW Eurodrive · MOVIMOT MM..C

¿Qué significa 91 ?

This fault is generated by the bus module and indicates an issue with the RS-485 communication link between the fieldbus gateway and the MOVIMOT® unit, typically stemming from electrical connection problems.

Causas comunes

  • Faulty electrical connection (RS-485) between the fieldbus gateway and MOVIMOT® (interrupted or switched cable).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the electrical connection (RS-485) between the fieldbus gateway and MOVIMOT® for continuity and correct wiring.

  2. 2

    Note: The fault automatically resets once the cause is removed; a reset via control word is not possible.

Ver todos los códigos en este manual (21)