Traduciendo...
11
Thermal overload of the output stage or internal unit error
SEW Eurodrive · MOVIFIT-FC Inverter
¿Qué significa 11 ?
The output stage of the unit has experienced thermal overload, or an internal error has occurred. This suggests that the operating temperature of the output stage is too high due to ambient conditions, inadequate heat dissipation, or excessive drive load, risking hardware damage.
Causas comunes
- Output stage overheating due to sustained high load.
- Internal fault within the power module's heatsink monitoring.
- Fan failure or blockage affecting heatsink cooling.
- Parameter P0626 (output stage thermal model) inaccurate.
- Overcurrent condition leading to output stage stress.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Lower the ambient temperature surrounding the unit.
- 2
Ensure proper ventilation around the unit to prevent heat build-up.
- 3
Reduce the mechanical load on the drive.
- 4
Reset the fault by switching off the DC 24 V supply voltage.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: SEW Eurodrive MOVIFIT-FC Inverter