Permanent low level in data line
SEW Eurodrive · MOVIDRIVE system
¿Qué significa F13.19 ?
The data signal from Encoder 1 is persistently at a low level. This typically points to a wiring issue or a defect within the encoder unit, resulting in lost or incorrect position feedback and impacting precise drive control.
Causas comunes
- Open circuit in the Encoder 1 data line (DATA+) or DATA- wiring between the encoder and the drive input terminal X1.
- Short circuit between the Encoder 1 data line (DATA+) or DATA- and 0V (ground) or shield.
- Internal failure of the Encoder 1 output stage, leading to a collapsed data signal.
- Insufficient encoder supply voltage (e.g., below 8VDC) provided by the drive's 10V or 24V supply to Encoder 1.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Power down the drive, disconnect Encoder 1 cable from terminal X1, and measure resistance between DATA+ and 0V.
- 2
Verify continuity of the Encoder 1 data lines (DATA+ and DATA-) and their respective return paths from encoder connector to drive terminal X1 using a multimeter.
- 3
Measure the supply voltage for Encoder 1 at the encoder's power input terminals (e.g., +10V or +24V to 0V).
- 4
Using an oscilloscope, monitor the data line signal (DATA+ and DATA- differential) at terminal X1 while slowly rotating the motor shaft.
- 5
Exchange Encoder 1 with a known-good encoder of the same type and test system operation.